This blog is all about Basic Electrical Engineering recommended to all beginners. Daily Updates
Friday, 4 July 2014
Ohm's Law
Whenever electric current flows through a conductor, the following three factors are present :
1. The pressure or potential difference V across the conductor (measured in volts) causing current to flow.
2. The opposition or resistance R of the conductor (measured in ohms) which must be overcome.
3. The current strength I (measured in amperes) which is maintained in the conductor as a result of pressure overcoming the resistance.
2. The opposition or resistance R of the conductor (measured in ohms) which must be overcome.
3. The current strength I (measured in amperes) which is maintained in the conductor as a result of pressure overcoming the resistance.
There exists a definite relationship between the three quantities involved and is known as Ohm's Law. It may be stated Thus :
"The ratio of potential difference (V) between any two points of a conductor to the current (I) flowing between them is constant, provided the temperature of the conductor doesn't change"
In other words, V/I = Constant or V/I = R
where R is the resistance of the conductor between the two points considered.
OR
" According to ohms law, the flowing through a conductor is directly proportional to the potential difference, across the ends of the conductor and inversely proportional to the conductor resistance."
i.e.., I α V and I α 1/R
where, I is the current, V is the voltage and R is the resistance of the conductor material.
thus
I α V/R
OR
"At constant temperature the current flowing through a conductor is directly proportional to the potential difference between its ends."
I α V ; V α I ; V = IR ;
Where R is a constant known as the resistance of the conductor.
OR
" The current is directly proportional to the voltage and inversely proportional to the resistance when the temperature remains constant."
i.e.., I = V/R
Voltage Divider Formula
It's used for finding voltage drops across different resistance connected in series. Since in a series circuit, same current flows through each resistor, voltage drops are directly proportional to their resistance
R = R1+R2+R3
V1 = VxR1/R
V2 = VxR2/R
V3 = VxR3/R
V = V1+V2+V3
Kirchhoff's First Laws or Point Law or Current Law (KCL)
These laws are more comprehensive than ohm's law and are used for solve electrical networks
It states that:
"in any network of conductors, the algebraic sum of the current meeting at a point (or junction) is zero."
OR
"the total current leaving a junction is equal to the total current entering the junction."
Incoming currents = outgoing currents
ΣI = 0 .... at a junction
It states that:
"in any network of conductors, the algebraic sum of the current meeting at a point (or junction) is zero."
OR
"the total current leaving a junction is equal to the total current entering the junction."
Incoming currents = outgoing currents
ΣI = 0 .... at a junction
Utilization Categories
utilization categories are defined by IEC (International Electrotechnical Commission) standards and indicate the type of electrical load and duty cycle of the loads to ease selection of contactors and relays.
AC1 Non-inductive or slightly inductive loads, example: resistive furnaces, heaters
AC2 Slip-ring motors: switching off
AC3 Squirrel-cage motors: starting, switches off motors during running time
AC4 Squirrel-cage motors: starting, plugging, inching
AC5a Switching of discharge lamps
AC5b Switching of incandescent lamps
AC6a Switching of transformers
AC6b Switching of capacitor banks
AC7a Slightly inductive loads in household appliances: examples: mixers, blenders
AC7b Motor-loads for household appliances: examples: fans, central vacuum
AC8a Hermetic refrigerant compressor motor control with manual resetting overloads
AC8b Hermetic refrigerant compressor motor control with automatic resetting overloads
AC12 Control of resisitive loads and solid state loads with opto-coupler isolation
AC13 Control of solid state loads with transformer isolation
AC14 Control of small electromagnetic loads
AC15 Control of A.C. electromagnetic loads
AC20 Connecting and disconnecting under no-load conditions
AC21 Switching of resistive loads, including moderate overloads
AC22 Switching of mixed resistive and inductive loads, including moderate overloads
AC23 Switching of motor loads or other highly inductive loads
A Protection of circuits, with no rated short-time withstand current
B Protection of circuits, with a rated short-time withstand current
DC1 Non Inductive or slightly inductive loads, resistance furnaces, heaters
DC3 Shunt-motors, starting, plugging(1), inching(2), dynamic breaking of motors
DC5 Series-motors, starting, plugging(1), inching(2), dynamic breaking of motors
DC6 Switching of incandescent lamps
DC12 Control of resistive loads and solid state loads with opto-coupler isolation
DC13 Control of D.C. electromagnetics
DC14 Control of D.C. electromagnetic loads having economy resistors in the circuit
DC20 Connecting and disconnecting under no-load conditions
DC21 Switching of resistive loads, including moderate overloads
DC22 Switching of mixed resistive and inductive loads, including moderate overloads (i.e. shunt motors)
DC23 Switching of highly inductive loads (i.e. series motors)
The standard utilization categories defines the current making and breaking values for contactors. they depend on the following..
1. Which type of load to be controlled (squirrel cage or slip ring induction motor, resistors)
2. The operating cycle conditions - Motor running, reverse operation, stalled or starting, counter current braking.
AC-1 - Non-inductive or slightly inductive loads
Ex : resistive load, heating, distribution.
AC-2 - Starting of slip-ring motors
AC-3 - Starting of squirrel-cage motors and switching off only after the motor is up to speed. Make Locked Rotor Amps (LRA), Break Full Load Amps (FLA)
Ex : all squirrel cage motors, lifts, escalators, conveyors, bucket elevators, compressors, pumps, mixers, air conditioning units, etc.
AC-4 - Starting of squirrel-cage motors with inching and plugging duty. Rapid Start/Stop. (Make and Break LRA)
AC-11 - Auxiliary (control) circuits
AC1 Non-inductive or slightly inductive loads, example: resistive furnaces, heaters
AC2 Slip-ring motors: switching off
AC3 Squirrel-cage motors: starting, switches off motors during running time
AC4 Squirrel-cage motors: starting, plugging, inching
AC5a Switching of discharge lamps
AC5b Switching of incandescent lamps
AC6a Switching of transformers
AC6b Switching of capacitor banks
AC7a Slightly inductive loads in household appliances: examples: mixers, blenders
AC7b Motor-loads for household appliances: examples: fans, central vacuum
AC8a Hermetic refrigerant compressor motor control with manual resetting overloads
AC8b Hermetic refrigerant compressor motor control with automatic resetting overloads
AC12 Control of resisitive loads and solid state loads with opto-coupler isolation
AC13 Control of solid state loads with transformer isolation
AC14 Control of small electromagnetic loads
AC15 Control of A.C. electromagnetic loads
AC20 Connecting and disconnecting under no-load conditions
AC21 Switching of resistive loads, including moderate overloads
AC22 Switching of mixed resistive and inductive loads, including moderate overloads
AC23 Switching of motor loads or other highly inductive loads
A Protection of circuits, with no rated short-time withstand current
B Protection of circuits, with a rated short-time withstand current
DC1 Non Inductive or slightly inductive loads, resistance furnaces, heaters
DC3 Shunt-motors, starting, plugging(1), inching(2), dynamic breaking of motors
DC5 Series-motors, starting, plugging(1), inching(2), dynamic breaking of motors
DC6 Switching of incandescent lamps
DC12 Control of resistive loads and solid state loads with opto-coupler isolation
DC13 Control of D.C. electromagnetics
DC14 Control of D.C. electromagnetic loads having economy resistors in the circuit
DC20 Connecting and disconnecting under no-load conditions
DC21 Switching of resistive loads, including moderate overloads
DC22 Switching of mixed resistive and inductive loads, including moderate overloads (i.e. shunt motors)
DC23 Switching of highly inductive loads (i.e. series motors)
The standard utilization categories defines the current making and breaking values for contactors. they depend on the following..
1. Which type of load to be controlled (squirrel cage or slip ring induction motor, resistors)
2. The operating cycle conditions - Motor running, reverse operation, stalled or starting, counter current braking.
AC-1 - Non-inductive or slightly inductive loads
Ex : resistive load, heating, distribution.
AC-2 - Starting of slip-ring motors
AC-3 - Starting of squirrel-cage motors and switching off only after the motor is up to speed. Make Locked Rotor Amps (LRA), Break Full Load Amps (FLA)
Ex : all squirrel cage motors, lifts, escalators, conveyors, bucket elevators, compressors, pumps, mixers, air conditioning units, etc.
AC-4 - Starting of squirrel-cage motors with inching and plugging duty. Rapid Start/Stop. (Make and Break LRA)
AC-11 - Auxiliary (control) circuits
ANSI Device Numbers
In the design of electrical power systems, the ANSI (American National Standards Institute) Standard Device Numbers (ANSI /IEEE Standard C37.2) denote what features a protective device supports (such as a relay or circuit breaker). These types of devices protect electrical systems and components from damage when an unwanted event occurs, such as an electrical fault. Device numbers are used to identify the functions of devices shown on a schematic diagram. Function descriptions are given in the standard.
List of device numbers and acronyms
1 – Master Element
Any initiating Device will be term as master element. Control Switches, voltage relays, Current Sensors etc. This device serves may be directly or it will operate some other protective device and will place equipment in or out of protection.
Ex: TNC switch ( Trip Neutral Close) to act as breaker control switch. So TNC is master element for Breaker.
2 – Time Delay Starting or Closing Relay
3 – Checking or Interlocking Relay
4 – Master Contactor
5 – Stopping Device
6 – Starting Circuit Breaker
7 – Rate of Change Relay
8 – Control Power Disconnecting Device
9 – Reversing Device
10 – Unit Sequence Switch
11 – Multi-function Device
12 – Overspeed Device
13 – Synchronous-speed Device
14 – Underspeed Device
15 – Speed – or Frequency, Matching Device
16 – Data Communications Device
17 – Shunting or Discharge Switch
18 – Accelerating or Decelerating Device
19 – Starting to Running Transition Contactor
20 – Electrically Operated Valve
21 – Distance Relay
22 – Equalizer Circuit Breaker
23 – Temperature Control Device
24 – Volts Per Hertz Relay
25 – Synchronizing or Synchronism-Check Device
26 – Apparatus Thermal Device
27 – Undervoltage Relay
28 – Flame detector
29 – Isolating Contactor or Switch
30 – Annunciator Relay
31 – Separate Excitation Device
32 – Directional Power Relay
33 – Position Switch
34 – Master Sequence Device
35 – Brush-Operating or Slip-Ring Short-Circuiting Device
36 – Polarity or Polarizing Voltage Devices
37 – Undercurrent or Underpower Relay
38 – Bearing Protective Device
39 – Mechanical Condition Monitor
40 – Field (over/under excitation) Relay
41 – Field Circuit Breaker
42 – Running Circuit Breaker
43 – Manual Transfer or Selector Device
44 – Unit Sequence Starting Relay
45 – Abnormal Atmospheric Condition Monitor
46 – Reverse-phase or Phase-Balance Current Relay
47 – Phase-Sequence or Phase-Balance Voltage Relay
48 – Incomplete Sequence Relay
49 – Machine or Transformer, Thermal Relay
50 – Instantaneous Overcurrent Relay
51 – AC Inverse Time Overcurrent Relay
52 – AC Circuit Breaker
53 – Exciter or DC Generator Relay
54 – Turning Gear Engaging Device
55 – Power Factor Relay
56 – Field Application Relay
57 – Short-Circuiting or Grounding Device
58 – Rectification Failure Relay
59 – Overvoltage Relay
60 – Voltage or Current Balance Relay
61 – Density Switch or Sensor
62 – Time-Delay Stopping or Opening Relay
63 – Pressure Switch
64 – Ground Detector Relay
65 – Governor
66 – Notching or Jogging Device
67 – AC Directional Overcurrent Relay
68 – Blocking or "Out-of-Step" Relay
69 – Permissive Control Device
70 – Rheostat
71 – Liquid Level Switch
72 – DC Circuit Breaker
73 – Load-Resistor Contactor
74 – Alarm Relay
75 – Position Changing Mechanism
76 – DC Overcurrent Relay
77 – Telemetering Device
78 – Phase-Angle Measuring Relay
79 – AC Reclosing Relay
80 – Flow Switch
81 – Frequency Relay
82 – DC Reclosing Relay
83 – Automatic Selective Control or Transfer Relay
84 – Operating Mechanism
85 – Communications,Carrier or Pilot-Wire Relay
86 – Lockout Relay
87 – Differential Protective Relay
88 – Auxiliary Motor or Motor Generator
89 – Line Switch
90 – Regulating Device
91 – Voltage Directional Relay
92 – Voltage and Power Directional Relay
93 – Field Changing Contactor
94 – Tripping or Trip-Free Relay
95 – For specific applications where other numbers are not suitable
96 – For specific applications where other numbers are not suitable
97 – For specific applications where other numbers are not suitable
98 – For specific applications where other numbers are not suitable
99 – For specific applications where other numbers are not suitable
AFD – Arc Flash Detector
CLK – Clock or Timing Source
DDR – Dynamic Disturbance Recorder
DFR – Digital Fault Recorder
ENV – Environmental Data
HIZ – High Impedance Fault Detector
HMI – Human Machine Interface
HST – Historian
LGC – Scheme Logic
MET – Substation Metering
PDC – Phasor Data Concentrator
PMU – Phasor Measurement Unit
PQM – Power Quality Monitor
RIO – Remote Input/Output Device
RTU – Remote Terminal Unit/Data Concentrator
SER – Sequence of Events Recorder
TCM – Trip Circuit Monitor
SOTF – Switch On To Fault
A suffix letter or number may be used with the device number. for example, suffix N is used if the device is connected to a Neutral wire (example: 59N in a relay is used for protection against Neutral Displacement) and suffixes X,Y,Z are used for auxiliary devices. Similarly, the "G" suffix denotes a "ground", hence a "51G" is a time over current ground relay. Suffix numbers are used to distinguish multiple "same" devices in the same equipment such as 51-1, 51–2.
Device numbers may be combined if the device provides multiple functions, such as the instantaneous/time-delay AC over current relay denoted as 50/51.
For device 16, the suffix letters further define the device: the first suffix letter is 'S' for serial or 'E' for Ethernet. The subsequent letters are: 'C' security processing function (e.g. VPN, encryption), 'F' firewall or message filter, 'M' network managed function, 'R' router, 'S' switch and 'T' telephone component. Thus a managed Ethernet switch would be 16ESM.
Types of Relay
First Letter - Operation Quantity
A - Phase angle comparison
B - Balanced Current
C - Current (Amps)
D - Differential
E - Direction
F - Frequency
K - Rate of rise of current
M - Manual
O - Oil Pressure
P - Poly phase VA
R - Reactive VA
S - Slip Frequency
T - Temperature
V - Potential
W - Watts
X - Reactance
Y - Admittance (Conductance)
Z - Impedance
Second Letter - Measurement
A - Attracted armature
B - Buchholz
C - Induction
D - Induction Disc
G - Galvanometer
I - Transmitter
J - Mixed Types
M - Magnet (polarized)
P - Plug
R - Rectifier
S - Synchronized Motor
T - Transistor
W - Weight (Gravity)
Third Letter - Application
A - Auxiliary
B - Testing
C - Carrier or Counting
D - Directional
E - Earth/Ground
F - Plug or Alarm Indicator
G - General or Generator
H - Harmonic Restricted
J - Tripping
JE - Tripping (Electrical Reset)
JM - Tripping (Manual Reset)
JS - Tripping (Self)
JC - Tripping (Conductor)
K - Check Alarm
L - Local Limiting
M - Same Phi or motor
N - Negative Sequence
O - Out of Step
P - Potential Failure
R - Re-closing
S - Synchronizing
T - Timer or Transformer
U - Definite Time
V - Voltage Resistant
W - Piolet Wire
WA - Interposing
WS - Inter-tripping
X - Supervisory
Y - Flash Back (Black Fire)
Z - Special Application
Z0 - Zero Sequence
Examples :
CDG - Current (operation), Disc(Measurement), General Purpose(Application)
CAG - Current (operation), Attracted armature(Measurement), General Purpose(Application)
VAJ - Potential (operation), Attracted armature(Measurement), Tripping(Application)
VTT - Potential (operation), Transmitter(Measurement), Transformer(Application)
VAZ - Potential (operation), Attracted armature(Measurement), Special Application
VAA - Potential (operation), Attracted armature(Measurement), Auxiliary (Application)
A - Phase angle comparison
B - Balanced Current
C - Current (Amps)
D - Differential
E - Direction
F - Frequency
K - Rate of rise of current
M - Manual
O - Oil Pressure
P - Poly phase VA
R - Reactive VA
S - Slip Frequency
T - Temperature
V - Potential
W - Watts
X - Reactance
Y - Admittance (Conductance)
Z - Impedance
Second Letter - Measurement
A - Attracted armature
B - Buchholz
C - Induction
D - Induction Disc
G - Galvanometer
I - Transmitter
J - Mixed Types
M - Magnet (polarized)
P - Plug
R - Rectifier
S - Synchronized Motor
T - Transistor
W - Weight (Gravity)
Third Letter - Application
A - Auxiliary
B - Testing
C - Carrier or Counting
D - Directional
E - Earth/Ground
F - Plug or Alarm Indicator
G - General or Generator
H - Harmonic Restricted
J - Tripping
JE - Tripping (Electrical Reset)
JM - Tripping (Manual Reset)
JS - Tripping (Self)
JC - Tripping (Conductor)
K - Check Alarm
L - Local Limiting
M - Same Phi or motor
N - Negative Sequence
O - Out of Step
P - Potential Failure
R - Re-closing
S - Synchronizing
T - Timer or Transformer
U - Definite Time
V - Voltage Resistant
W - Piolet Wire
WA - Interposing
WS - Inter-tripping
X - Supervisory
Y - Flash Back (Black Fire)
Z - Special Application
Z0 - Zero Sequence
Examples :
CDG - Current (operation), Disc(Measurement), General Purpose(Application)
CAG - Current (operation), Attracted armature(Measurement), General Purpose(Application)
VAJ - Potential (operation), Attracted armature(Measurement), Tripping(Application)
VTT - Potential (operation), Transmitter(Measurement), Transformer(Application)
VAZ - Potential (operation), Attracted armature(Measurement), Special Application
VAA - Potential (operation), Attracted armature(Measurement), Auxiliary (Application)
Subscribe to:
Posts (Atom)